Features
1. Basic temperature transmitter offers a reliable solution for temperature monitoring points
2. Standard transmitter design provides flexible and reliable performance in process environments
3. Experience lower over-all installation costs when compared to wiring sensor directly, reducing the need for expensive extension wires and multiplexer
4. Explore the benefits of a Complete Point Solution from Rosemount Temperature
5.Experience global consistency and local support from numerous worldwide Rosemount Temperature manufacturing sites
Specification
Inputs: User-selectable; sensor terminals rates to 42.4 Vdc.
Output: 2-wire 4-20 mA, linear with temperature or input; digital output signal superimposed on 4-20 ma signal, available for a Field Communicator or control system interface.
Isolation: Input/output isolation tested to 500 Vac rms (707 Vdc) at 50/60Hz.
Power supply: An external power supply is required for HART devices. The transmitter operates on 12.0 to 42.4 Vdc transmitter terminal voltage with load resistance between 250 and 1100 ohms. A minimum of 17.75 Vdc power supply is required with a load of 250 ohms. Transmitter power terminals are rated to 42.4 Vdc.
Humidity limits: 0-99% relative humidity, non-condensing.
Temperature limits: Operating Limit: –40 to 850C (–40 to 1850F); Storage Limit: –50 to 1200C (–58 to 2480F).
Update rate: Less than 0.5 seconds
Damping: 32 seconds maximum. 5 seconds default
Turn-on time: Performance within specifications in less than five seconds after power is applied to transmitter, when damping value is set to zero seconds.
Update rate: Less than 0.5 seconds
Damping: 32 seconds maximum; five seconds default
Dimension